Wire Size Chart (AWG)
An AWG wire size chart with the diameter, cross-section, amp rating and maximum fuse for every gauge from 18 AWG to 4/0 AWG, for marine, RV and vehicle wiring.
AWG wire size chart
Diameter and area are for the bare conductor. Ampacity is for 105 °C insulated cable at 30 °C ambient. The last column is the longest one-way run for a 20 A load at 12 V with 3% voltage drop.
| Gauge | Diameter (in) | Diameter (mm) | Area (mm²) | Ampacity (A) | Max run, 12V 20A (ft) |
|---|---|---|---|---|---|
| 18 AWG | 0.040 | 1.02 | 0.8 | 20 | 1.4 |
| 16 AWG | 0.051 | 1.29 | 1.3 | 25 | 2.2 |
| 14 AWG | 0.064 | 1.63 | 2.1 | 35 | 3.5 |
| 12 AWG | 0.081 | 2.05 | 3.3 | 45 | 5.5 |
| 10 AWG | 0.102 | 2.59 | 5.3 | 60 | 8.7 |
| 8 AWG | 0.128 | 3.26 | 8.4 | 80 | 13.9 |
| 6 AWG | 0.162 | 4.12 | 13.3 | 120 | 22.1 |
| 4 AWG | 0.204 | 5.19 | 21.2 | 160 | 35.1 |
| 2 AWG | 0.258 | 6.54 | 33.6 | 210 | 55.8 |
| 1 AWG | 0.289 | 7.35 | 42.4 | 245 | 70.3 |
| 1/0 AWG | 0.325 | 8.25 | 53.5 | 285 | 88.7 |
| 2/0 AWG | 0.365 | 9.27 | 67.4 | 330 | 111.9 |
| 3/0 AWG | 0.410 | 10.40 | 85.0 | 385 | 141.1 |
| 4/0 AWG | 0.460 | 11.68 | 107.2 | 445 | 177.9 |
Wire size and fuse chart
The largest fuse each gauge supports. "Fuse at ampacity" is the largest standard rating at or below the wire's ampacity; "maximum fuse" applies the 150% allowance used for DC circuits.
| Wire gauge | Ampacity (A) | Fuse at ampacity (A) | Maximum fuse (A) | Maximum in engine space (A) |
|---|---|---|---|---|
| 18 AWG | 20 | 20 | 30 | 25 |
| 16 AWG | 25 | 25 | 30 | 30 |
| 14 AWG | 35 | 30 | 50 | 40 |
| 12 AWG | 45 | 40 | 60 | 50 |
| 10 AWG | 60 | 60 | 90 | 70 |
| 8 AWG | 80 | 80 | 110 | 100 |
| 6 AWG | 120 | 110 | 175 | 150 |
| 4 AWG | 160 | 150 | 225 | 200 |
| 2 AWG | 210 | 200 | 300 | 250 |
| 1 AWG | 245 | 225 | 350 | 300 |
| 1/0 AWG | 285 | 275 | 400 | 350 |
| 2/0 AWG | 330 | 325 | 450 | 400 |
| 3/0 AWG | 385 | 350 | 500 | 450 |
| 4/0 AWG | 445 | 400 | 600 | 500 |
How AWG sizes work
American Wire Gauge runs backwards: the smaller the number, the thicker the wire. Every three steps roughly doubles the copper area. Sizes larger than 1 AWG are written 1/0, 2/0, 3/0 and 4/0.
To pick a size for a specific current and length, use the wire size calculator or the wire gauge calculator.
Cable, lugs and tools
Wire size questions
What gauge wire do I need for 30 amps?
For marine and RV cable with 105 °C insulation, 14 AWG is rated for 35 A, but voltage drop usually calls for larger: at 12 V, 30 A over 10 feet needs 6 AWG. Household 30 A circuits use 10 AWG under the NEC.
Which is thicker, 12 gauge or 14 gauge?
12 AWG is thicker: 3.3 mm² against 2.1 mm² for 14 AWG.
How many amps can 4 AWG wire carry?
160 A on 105 °C insulated cable outside engine spaces, and 136 A inside an engine space.
What is the largest standard battery cable?
4/0 AWG, with a cross-section of 107 mm² and an ampacity of 445 A.