Fuse Size Calculator
Find the right fuse or breaker size for a DC circuit. Enter the load in amps or watts and the wire gauge, and the calculator returns the smallest fuse that will not nuisance-trip and the largest fuse that still protects the wire.
70 ARecommended fuse size
- Load current
- 50 A
- Smallest fuse (125% of load)
- 70 A
- Largest fuse for this wire
- 225 A
- Wire ampacity
- 160 A
First-pass guidance following ABYC E-11 practice for DC circuits. Always follow the fuse rating specified by the equipment manufacturer, and check that the fuse's voltage and interrupt ratings suit your battery bank.
Parts for this circuit
How to size a fuse
A fuse protects the wire, not the device. Its job is to open before the cable overheats in a short circuit or overload. That gives a fuse two limits. It must be large enough to carry the normal load without nuisance-tripping, which means at least 125% of the continuous current. And it must be small enough to protect the cable, which means no more than 150% of the wire's ampacity.
Any standard fuse rating between those two limits is acceptable. The calculator recommends the smallest one, because a closer fuse reacts faster to a fault. If no rating fits between the limits, the wire is too small for the load and needs to go up a gauge.
Place the fuse as close to the power source as possible, since the cable between the battery and the fuse is unprotected. For lithium battery banks, use a Class T fuse on the main battery cable: lithium batteries can deliver very high short-circuit currents, and Class T fuses have the interrupt rating to clear them safely.
Fuse size chart by wire gauge
For 105 °C insulated cable at 30 °C ambient. "Fuse at ampacity" is the largest standard rating at or below the wire's ampacity; "maximum fuse" applies the 150% allowance.
| Wire gauge | Ampacity (A) | Fuse at ampacity (A) | Maximum fuse (A) | Maximum in engine space (A) |
|---|---|---|---|---|
| 18 AWG | 20 | 20 | 30 | 25 |
| 16 AWG | 25 | 25 | 30 | 30 |
| 14 AWG | 35 | 30 | 50 | 40 |
| 12 AWG | 45 | 40 | 60 | 50 |
| 10 AWG | 60 | 60 | 90 | 70 |
| 8 AWG | 80 | 80 | 110 | 100 |
| 6 AWG | 120 | 110 | 175 | 150 |
| 4 AWG | 160 | 150 | 225 | 200 |
| 2 AWG | 210 | 200 | 300 | 250 |
| 1 AWG | 245 | 225 | 350 | 300 |
| 1/0 AWG | 285 | 275 | 400 | 350 |
| 2/0 AWG | 330 | 325 | 450 | 400 |
| 3/0 AWG | 385 | 350 | 500 | 450 |
| 4/0 AWG | 445 | 400 | 600 | 500 |
Fuse sizing questions
What size fuse do I need for a 100 amp load?
At least 125 A, which is the first standard rating above 125% of the load. The wire must also be rated for it: 2 AWG cable (210 A ampacity) can be protected by a fuse up to 300 A, so a 125 A fuse on 2 AWG works.
What size fuse for 10 AWG wire?
10 AWG marine cable is rated for 60 A, so a 60 A fuse is the usual choice and 90 A is the maximum. Pick the smallest rating that is still at least 125% of your load.
What size fuse for a 2000 watt inverter on 12 volts?
2000 W at 12 V is about 167 A before inverter losses, so the smallest suitable standard fuse is 225 A. Inverter manufacturers publish a recommended fuse and cable size for each model; follow that figure when it is larger.
Should the fuse match the wire or the device?
The wire. Size the fuse so it never exceeds what the cable can safely carry. If the device needs its own lower-rated protection, it will usually have a built-in fuse or specify one in its manual.