Wire Gauge Calculator

Pick a wire gauge to see how many amps it can carry, how far it can run before voltage drop becomes a problem, and its diameter and cross-section in inches and millimeters. Covers 18 AWG through 4/0 AWG.

Used to work out the longest run for this gauge.

60 AMaximum current for 10 AWG

Longest one-way run at this load
8.7 ft
Largest fuse for this wire
90 A
Conductor diameter
0.102 in (2.59 mm)
Cross-section
5.3 mm²

Ampacity for 105 °C insulated tinned copper cable at 30 °C ambient, as used in marine, RV and vehicle wiring. Household cable types are rated lower; follow the NEC for building wiring.

How wire gauge works

American Wire Gauge (AWG) runs backwards: the smaller the number, the thicker the wire. Every three gauge steps roughly doubles the copper cross-section, so 7 AWG has about twice the area of 10 AWG. Past 1 AWG the sizes continue as 1/0 ("one-aught"), 2/0, 3/0 and 4/0, which is the largest standard battery cable.

A thicker wire does two things. It carries more current before it overheats (its ampacity), and it has lower resistance, so it loses less voltage over a long run. On low-voltage DC systems the second limit usually bites first: a 12 AWG wire can carry 45 A without overheating, but at 12 V and 20 A it can only run about 5.5 feet before losing more than 3% of the voltage.

AWG wire gauge chart

Diameter and area are for the bare conductor. The last column is the longest one-way run for a 20 A load at 12 V with 3% voltage drop.

GaugeDiameter (in)Diameter (mm)Area (mm²)Ampacity (A)Max run, 12V 20A (ft)
18 AWG0.0401.020.8201.4
16 AWG0.0511.291.3252.2
14 AWG0.0641.632.1353.5
12 AWG0.0812.053.3455.5
10 AWG0.1022.595.3608.7
8 AWG0.1283.268.48013.9
6 AWG0.1624.1213.312022.1
4 AWG0.2045.1921.216035.1
2 AWG0.2586.5433.621055.8
1 AWG0.2897.3542.424570.3
1/0 AWG0.3258.2553.528588.7
2/0 AWG0.3659.2767.4330111.9
3/0 AWG0.41010.4085.0385141.1
4/0 AWG0.46011.68107.2445177.9

Wire gauge questions

How many amps can 10 gauge wire handle?

10 AWG marine-grade cable with 105 °C insulation is rated for 60 A outside engine spaces and 51 A inside them. Household 10 AWG cable is limited to 30 A by the NEC because it uses lower-temperature insulation.

Which is thicker, 4 AWG or 6 AWG?

4 AWG is thicker. Gauge numbers run backwards, so a lower number means a larger conductor: 4 AWG is 21.2 mm² and 6 AWG is 13.3 mm².

What does 1/0 or 2/0 wire mean?

Sizes larger than 1 AWG are written with zeros: 1/0 ("one-aught"), 2/0, 3/0 and 4/0. Each step is larger than the last, and 4/0 is the heaviest standard battery cable at 107 mm².

How far can I run 12 gauge wire at 12 volts?

With a 20 A load and a 3% voltage drop limit, about 5.5 feet one way. Lower currents allow longer runs: halve the current and the distance doubles. Enter your own load above to check.