Battery Cable Size Chart
Battery cable sizes for 12V, 24V and 48V systems by current and cable length. Each chart gives the minimum tinned copper cable (AWG) that carries the current safely and keeps voltage drop to 3% or less.
How to read the charts
Find the row for the current your cable carries and the column for the one-way length from the battery to the device. The chart gives the smallest AWG size that passes two checks: the cable's ampacity covers the current, and the round-trip voltage drop stays at 3% or less. A dash means a single cable is not enough: use parallel cables or a higher system voltage.
For a length or current between the values shown, use the DC wire size calculator, and size the fuse with the fuse size calculator.
12V battery cable size chart
| Current | 5 ft | 10 ft | 15 ft | 20 ft | 25 ft |
|---|---|---|---|---|---|
| 10 A | 14 | 12 | 10 | 8 | 8 |
| 20 A | 12 | 8 | 6 | 6 | 4 |
| 30 A | 10 | 6 | 4 | 4 | 2 |
| 40 A | 8 | 6 | 4 | 2 | 2 |
| 50 A | 8 | 4 | 2 | 2 | 1 |
| 75 A | 6 | 2 | 1 | 1/0 | 2/0 |
| 100 A | 4 | 2 | 1/0 | 2/0 | 3/0 |
| 150 A | 2 | 1/0 | 3/0 | 4/0 | — |
| 200 A | 2 | 2/0 | 4/0 | — | — |
| 250 A | 1/0 | 3/0 | — | — | — |
| 300 A | 2/0 | 4/0 | — | — | — |
24V battery cable size chart
| Current | 5 ft | 10 ft | 15 ft | 20 ft | 25 ft |
|---|---|---|---|---|---|
| 10 A | 18 | 14 | 12 | 12 | 10 |
| 20 A | 14 | 12 | 10 | 8 | 8 |
| 30 A | 12 | 10 | 8 | 6 | 6 |
| 40 A | 12 | 8 | 6 | 6 | 4 |
| 50 A | 10 | 8 | 6 | 4 | 4 |
| 75 A | 8 | 6 | 4 | 2 | 2 |
| 100 A | 6 | 4 | 2 | 2 | 1 |
| 150 A | 4 | 2 | 1 | 1/0 | 2/0 |
| 200 A | 2 | 2 | 1/0 | 2/0 | 3/0 |
| 250 A | 1/0 | 1/0 | 2/0 | 3/0 | 4/0 |
| 300 A | 2/0 | 2/0 | 3/0 | 4/0 | — |
48V battery cable size chart
| Current | 5 ft | 10 ft | 15 ft | 20 ft | 25 ft |
|---|---|---|---|---|---|
| 10 A | 18 | 18 | 16 | 14 | 14 |
| 20 A | 18 | 14 | 12 | 12 | 10 |
| 30 A | 14 | 12 | 10 | 10 | 8 |
| 40 A | 12 | 12 | 10 | 8 | 8 |
| 50 A | 10 | 10 | 8 | 8 | 6 |
| 75 A | 8 | 8 | 6 | 6 | 4 |
| 100 A | 6 | 6 | 6 | 4 | 4 |
| 150 A | 4 | 4 | 4 | 2 | 2 |
| 200 A | 2 | 2 | 2 | 2 | 1 |
| 250 A | 1/0 | 1/0 | 1/0 | 1/0 | 1/0 |
| 300 A | 2/0 | 2/0 | 2/0 | 2/0 | 2/0 |
Sizes are for 105 °C insulated tinned copper cable at 30 °C ambient, outside engine spaces. Shop battery cable and tinned copper lugs.
Cable, lugs and tools
Battery cable questions
What size battery cable do I need for 100 amps?
On a 12 V system, 100 A needs 4 AWG for a 5-foot run, 2 AWG for 10 feet, 1/0 AWG for 15 feet and 2/0 AWG for 20 feet.
What size cable for a 200 amp battery connection?
At 12 V, 200 A needs 2 AWG for 5 feet, 2/0 AWG for 10 feet and 4/0 AWG for 15 feet.
Do 24V and 48V systems need smaller cable?
Yes. The same power draws half the current at 24 V and a quarter at 48 V, and the voltage drop allowance is larger in volts, so cables can be much smaller.
Is the length one way or round trip?
One way, from the battery to the device. The charts already account for the return cable.