DC Wire Size Calculator
Find the right wire gauge and fuse size for 12V, 24V and 48V DC circuits in RVs, vans, boats and off-grid systems. Enter the load current and cable run, and the calculator checks both ampacity and voltage drop.
4 AWGRecommended minimum wire size
- Voltage drop
- 2.1%
- Wire ampacity
- 160 A
- Recommended fuse
- 70 A
- Largest fuse for this wire
- 225 A
First-pass sizing based on ABYC E-11 style ampacities for 105 °C insulated boat cable at 30 °C ambient. Always confirm against the equipment manufacturer's requirements and the applicable standard.
Parts for this circuit
How the wire size is calculated
A DC cable has to pass two checks. First, its ampacity (the current it can carry without overheating) must be at least the circuit current. Second, the voltage drop across the full round trip must stay within the allowance: 3% for critical circuits such as inverters, chargers and electronics, and 10% for non-critical loads. The calculator picks the smallest standard AWG size that passes both.
Voltage drop is calculated as current × conductor resistance × round-trip length ÷ system voltage. Low-voltage systems are the most sensitive: the same 50 A load over 10 feet needs a heavier cable at 12 V than at 24 V or 48 V, which is why many vans and boats move to higher-voltage battery banks.
The fuse recommendation follows the usual DC protection rule. The fuse must carry 125% of the continuous current so it does not nuisance-trip, and it may not exceed 150% of the wire's ampacity, so the fuse protects the cable.
12V battery cable size chart
Minimum tinned copper wire size (AWG) for a 12 V circuit with 3% maximum voltage drop, outside engine spaces. Lengths are one way. A dash means the run needs more than 4/0 AWG, parallel conductors, or a higher system voltage.
| Current | 5 ft | 10 ft | 15 ft | 20 ft | 25 ft |
|---|---|---|---|---|---|
| 10 A | 14 | 12 | 10 | 8 | 8 |
| 20 A | 12 | 8 | 6 | 6 | 4 |
| 30 A | 10 | 6 | 4 | 4 | 2 |
| 40 A | 8 | 6 | 4 | 2 | 2 |
| 50 A | 8 | 4 | 2 | 2 | 1 |
| 75 A | 6 | 2 | 1 | 1/0 | 2/0 |
| 100 A | 4 | 2 | 1/0 | 2/0 | 3/0 |
| 150 A | 2 | 1/0 | 3/0 | 4/0 | — |
| 200 A | 2 | 2/0 | 4/0 | — | — |
| 250 A | 1/0 | 3/0 | — | — | — |
| 300 A | 2/0 | 4/0 | — | — | — |
Wire gauge ampacity table
Allowable current for 105 °C insulated marine cable at 30 °C ambient, with tinned copper resistance at 20 °C.
| Wire size | Area (mm²) | Ampacity (A) | In engine space (A) | Ω per 1,000 ft |
|---|---|---|---|---|
| 18 AWG | 0.8 | 20 | 17 | 6.592 |
| 16 AWG | 1.3 | 25 | 21 | 4.146 |
| 14 AWG | 2.1 | 35 | 30 | 2.607 |
| 12 AWG | 3.3 | 45 | 38 | 1.640 |
| 10 AWG | 5.3 | 60 | 51 | 1.031 |
| 8 AWG | 8.4 | 80 | 68 | 0.649 |
| 6 AWG | 13.3 | 120 | 102 | 0.408 |
| 4 AWG | 21.2 | 160 | 136 | 0.257 |
| 2 AWG | 33.6 | 210 | 179 | 0.161 |
| 1 AWG | 42.4 | 245 | 208 | 0.128 |
| 1/0 AWG | 53.5 | 285 | 242 | 0.101 |
| 2/0 AWG | 67.4 | 330 | 281 | 0.080 |
| 3/0 AWG | 85.0 | 385 | 327 | 0.064 |
| 4/0 AWG | 107.2 | 445 | 378 | 0.051 |
Wire sizing questions
What size wire do I need for 100 amps at 12 volts?
For a 10-foot one-way run at 12 V with 3% voltage drop, use 2 AWG tinned copper. At 15 feet you need 1/0 AWG, and at 20 feet 2/0 AWG. Use the calculator above for your exact length.
Should I use the one-way or round-trip length?
Enter the one-way distance from the source to the load. The calculator doubles it, because current flows out on the positive cable and back on the negative.
When should I allow 3% versus 10% voltage drop?
Use 3% for anything sensitive to low voltage: inverters, chargers, DC-DC converters, panels, navigation and electronics. A 10% drop is acceptable for non-critical loads such as general lighting.
How do I size the fuse for a wire?
Choose a fuse rated at least 125% of the continuous current, and no larger than 150% of the wire's ampacity. Place it as close to the battery or power source as possible.
Why does tinned copper matter on boats and RVs?
Tinned copper strands resist corrosion in humid and salty environments, which keeps resistance low over the life of the installation. It has slightly higher resistance than bare copper, which the calculator accounts for.